How to Size Commercial Bathroom Exhaust Fans (2024 UMC, IMC & ASHRAE Guide)

Learn how to calculate commercial bathroom exhaust fan requirements using the 2024 Uniform Mechanical Code (UMC), International Mechanical Code (IMC), and ASHRAE 62.1. Includes step-by-step examples and practical CFM calculations.


Why Proper Bathroom Exhaust Fan Sizing Matters

When it comes to commercial restrooms—whether in office buildings, malls, or airports—sizing the exhaust fan correctly is more than just odor control. It’s about protecting indoor air quality (IAQ), preventing moisture-related damage, and ensuring compliance with the latest mechanical codes.

Undersized fans can cause:

  • Persistent odors
  • Excess humidity and condensation
  • Mold or mildew buildup
  • Damage to drywall, ceilings, and finishes

To avoid these issues, we follow updated guidelines from:

  • 2024 Uniform Mechanical Code (UMC)
  • 2024 International Mechanical Code (IMC)
  • ASHRAE Standard 62.1

Bathroom Exhaust Requirements per 2024 Code Updates

2024 Uniform Mechanical Code (UMC)

  • Light-use public restrooms: 50 CFM per water closet or urinal
  • Heavy-use areas (e.g., airports, stadiums): 70 CFM per fixture

2024 International Mechanical Code (IMC)

  • Continuous ventilation: 50 CFM per fixture
  • Intermittent ventilation: 70 CFM per fixture

🔍 Note: The IMC defines "intermittent" as fans operated via switch, sensor, or in sync with lighting. "Continuous" means the fan runs 24/7 or on a timer.

ASHRAE 62.1-2022 Highlights

  • Aligns with similar CFM per fixture rates
  • Emphasizes air change effectiveness and avoiding cross-contamination
  • Prioritizes balanced airflow and zone pressurization

Step-by-Step: How to Calculate Restroom Exhaust Airflow (CFM)

Let’s walk through an example based on a typical commercial building layout.

Men’s Public Restroom

  • 5 water closets
  • 2 urinals
  • Total: 7fixtures

Women’s Public Restroom

  • 5 water closets
  • Total: 5 fixtures

Step 1: Determine Applicable Code & Fan Operation Type

We’ll use IMC 2024 as the governing code and assume intermittent operation, meaning the fan activates with a light switch or occupancy sensor.

Step 2: Apply Correct Exhaust Rate

Under intermittent operation, the IMC calls for:

70 CFM per water closet or urinal

Step 3: Calculate Total Exhaust Airflow (CFM)

  • Men’s Room:7 fixtures × 70 CFM = 490 CFM

  • Women’s Room: 5 fixtures × 70 CFM = 350 CFM

Step 4: Provide Makeup Air

To maintain proper negative pressure and airflow direction, ASHRAE 62.1 recommends makeup air systems that prevent contaminants from migrating into clean areas.

Makeup Air Options:

  1. Transfer Air: Air pulled in from hallways or adjacent spaces via door undercuts or transfer grilles

  2. Dedicated Conditioned Air: Directly supplied to the restroom from the HVAC system
  3. Combination Method: Uses both transfer air and limited HVAC supply

Step 5: Select Exhaust Fans

Choose an exhaust fan with a capacity equal to or slightly higher than the total required CFM. Ensure your duct sizing and static pressure ratings are aligned with fan specs.

Summary & Best Practices

For private use restrooms the required exhaust is 25 CFM for continuous or 50 CFM for intermittent system operation.
  • Match your design to the intended usage (light vs. heavy)
  • Always confirm if the system runs continuously or intermittently
  • Reference UMC 2024, IMC 2024, and ASHRAE 62.1 for compliance
  • Don’t forget makeup air design to maintain airflow balance

Need More Help?

For detailed ventilation design, consult the full code texts:

  • 2024 IMC (ICC Official Site)
  • 2024 UMC (IAPMO Official Site)
  • ASHRAE 62.1 Standards

If you're an HVAC design professional or contractor, these guidelines ensure your restroom ventilation systems are safe, efficient, and code-compliant.