ASHRAE Air Changes Per Hour (ACH)
Air Changes per Hour (ACH) is a ventilation metric defined by ASHRAE as the number of times the entire volume of air within a space is replaced in one hour.
ACH Formula
ACH = (CFM × 60) / Room Volume (in cubic feet)
- CFM = Cubic Feet per Minute (airflow rate)
- Room Volume = Length × Width × Height
ACH Calculator
* According to ASHRAE Standard 62.1, ACH recommendations vary by occupancy type.
Ensure the calculated ACH aligns with the minimum ventilation requirements for your application.
Ensure the calculated ACH aligns with the minimum ventilation requirements for your application.
ASHRAE Guidelines for ACH
Space Type | Recommended ACH (Typical) | Standard |
---|---|---|
Office (General) | 2 – 4 ACH | ASHRAE 62.1 |
Classrooms (K-12) | 3 – 6 ACH | ASHRAE 62.1 |
Conference Rooms | 4 – 10 ACH | ASHRAE 62.1 |
Patient Rooms (Hospitals) | 6 ACH (min) | ASHRAE 170 |
Operating Rooms (Hospitals) | 15 – 20 ACH | ASHRAE 170 |
Bathrooms | 6 – 10 ACH | ASHRAE 62.1 |
Laboratories (General) | 6 – 12 ACH | ASHRAE 62.1 |
Isolation Rooms (Hospitals) | 12 ACH (min) | ASHRAE 170 |